After deciding to carry out combustible dust tests the first
thing you should do is to gather dust sample(s) and sent them to the lab,
right? Actually, no. NFPA 652 requires that a written sampling plan be
developed with a rational reason for why the sample locations were chosen. So
what is so important about a written sampling plan?
The purpose of the combustible dust tests is to determine
the hazards presented by the dust that is actually in your facility and in your
process. The actual hazard presented by YOUR dust may be substantially
different than in another facility handling the same type of dust but that has
a different process. For example, I have been in a facility that handles grain
where the grain goes directly from a storage bin into a process. In this case a
sample of grain from the storage bin taken from the storage bin accurately
reflected the dust in the system. At the same time a different facility across
town used the same grain (it actually came from the same source) but their
process included a hammer mill between the storage bin and the process. In this
case a sample of grain taken from the storage bin does not represent the hazard
in the system because the fugitive dust emanating from the hammer mill and the
product stream to the process were much smaller than the dust found in the
storage bin and had a much higher explosibility. (See previous entry.) While the grain in both facilities started out
the same, the hammer mill process changed hazards associated with the dust. The
end result was that the two facilities were very different.
This simple example helps demonstrate why a written plan is
required. A written plan requires time to be taken to evaluate and record the
reasons why a sample accurately reflects the hazards in a facility. A written
plan will help deflect/answer questions if an audit of system or safety
documentation were to occur. A non-existent or slipshod sampling plan will
leave many questions unanswered and leave the door wide open for further
inquiries. On the other hand, a well thought-out and written plan will provide
answers to many, if not all, of the auditor’s questions.
A blog covering a wide range of topics including Computational Fluid Dynamics (CFD), Finite Element Analysis (FEA), Industrial Ventilation, and other mechanical systems.
Thursday, July 27, 2017
Monday, July 24, 2017
Combustible Dust Testing Overview
According
to NFPA 652, it is the responsibility of the owner/operator of a facility to
determine if the dust in their facility is combustible/explosible or not. This
determination is made by collecting a sample of dust from the facility and
sending it to a lab for combustibility tests. The collection of the sample
needs to be performed following a written sampling plan. A more detailed
discussion of a sampling plan will be presented in a later entry. The following
outlines some of the most common dust tests that are available. Other tests may
be necessary depending upon the material in your facility.
Explosibility
Screening Test: Commonly called the “Go/No” Go test, this test determines if
the dust presents an explosion hazard. If the results from the test are
negative, i.e. the dust does not present an explosion hazard, no further action
is required other than documenting the fact that the dust is not explosive. If
the test is positive, i.e. the dust does present an explosion hazard, further
testing is required to characterize the explosion severity and risk. The test
procedure is described in ASTM 1226-12a.
Deflagration
Index (KSt): The deflagration index is a measure of how “explosive”
a material is. The value is determined from test data and is found using the
following relationship:
V = volume of the
test vessel
Maximum
Pressure (PMax): This is the maximum pressure created by a dust
explosion. This value is calculated with an optimal dust concentration, i.e.
the concentration that gives the highest pressure.
Minimum Explosible Concentration (MEC): This value indicates the minimum concentration of dust which can sustain a deflagration. If the concentration is too low, there is not enough energy released by a single dust particle to bridge that gap to the next particle. It is similar to the Lower Explosive Limit (LEL) or Lower Flammability Limit (LFL) of vapors. There are some important differences between the LEL and the MEC. However in a big picture sense they are equivalent.
Minimum Ignition Energy (MIE): This represents the minimum amount of energy required to ignite a dust cloud. The lower this value is the easier it is to ignite a dust cloud.
Minimum Explosible Concentration (MEC): This value indicates the minimum concentration of dust which can sustain a deflagration. If the concentration is too low, there is not enough energy released by a single dust particle to bridge that gap to the next particle. It is similar to the Lower Explosive Limit (LEL) or Lower Flammability Limit (LFL) of vapors. There are some important differences between the LEL and the MEC. However in a big picture sense they are equivalent.
Minimum Ignition Energy (MIE): This represents the minimum amount of energy required to ignite a dust cloud. The lower this value is the easier it is to ignite a dust cloud.
Friday, July 21, 2017
NFPA 652: Standard on Fundamentals of Combustible Dust
NFPA serves as the foundational NFPA document to guide the
control of the hazards associated with combustible dust. One of the key items
introduced by this standard is that it is the responsibility of the
owner/operator of a facility to determine if the dust in their facility is
combustible/explosible or not. This determination is made by collecting a
sample of dust from the facility and sending it to a lab for combustibility
tests. If the dust is not combustible, then the owner/operator has complied
with the standard (and probably the OSHA General Duty Clause) and the formal
documentation process concern combustible dust is over. (Please note that the
everyday aspects of safety still apply: housekeeping as an example. You can’t
leave piles of dust around even if it can’t explode.) If the dust IS
combustible, then further tests are required. In addition, the owner/operator
must carry out a formal Dust Hazard Analysis (DHA).
What is a DHA? In the simplest sense the DHA is a formal
process whose output is a document which describes/assesses the hazards present
in a facility, describes how the hazards will be controlled, eliminated, or
mitigated, and describes what management systems will be implemented to ensure
that the hazards continue to be controlled in the future. The hazard assessment
must be backed up by results from combustible dusts tests. The management
portion must include Standard Operating Procedures for items such as
housekeeping, preventative maintenance, and training.
The overall goal of the DHA is that the owner/operator of a facility
performs a legitimate and thorough evaluation and not just a cursory look at a
system. A thorough evaluation will find and control a lot of simple, easily
fixed risks (the “low hanging fruit”) which typically increases the safety of employees
operating a process or working in a facility.
Thursday, June 22, 2017
Flash Fire Demonstration Video
The previous posts were all about fire and dust. I wanted to post an example of a flash fire caused by a dust cloud.
This fireball was created with less than 1 teaspoon of dust. Imagine the size of the fire if hundreds of pounds of dust were ignited. Many of the deaths resulting from dust incidents are due to the burns from the flash fire not from injuries caused by an explosion. The happens so quickly there is no way to get out of the way of the flames. You will be suddenly engulfed in flame.
The purpose of the Dust Hazard Analysis (DHA) is to examine your facility and processes so that risks that can lead to flash fires are managed and controlled.
Monday, June 19, 2017
Why Dust Makes an Excellent Fuel
There are a lot of factors that affect how quickly a fuel
oxidizes, i.e. burns. In the following discussion we will assume everything
about the reaction is constant: the reaction rate, the fuel is homogeneous,
moisture content is the same, etc. These simplifications will help keep things
simple and allow us to concentrate on the major issue dust presents: incredibly large surface areas.
The burning reaction essentially takes place on the
surface of the fuel. As more surface is exposed to the oxidizing
environment the reaction takes place over a larger area, more material is
consumed in a shorter period of time and the burning rate increases. As an example, assume we have a perfectly
spherical fuel that has a diameter of 1 (of whatever unit you choose). The
surface area of that sphere will be 3.14159 square units of area.
Now assume that we have the same amount of fuel but this
time it is made up into four spheres, i.e. each sphere is ¼ the volume of the
original sphere. The surface area of the four spheres is 4.99 square units, or
an increase of approximately 58%. If the fuel is dispersed with the surrounding air the total surface area exposed to air is 58% more than with the original fuel and there is 58% more reaction locations. This increase in
reaction locations has the effect of increasing the reaction rate.
Now assume that we have the same amount of fuel made up into
25 identical spheres. The new surface area is 9.19 square units. This is almost
three times (2.92) the original area and will allow the reaction rate to be
approximately three times the original reaction rate.
Now assume that the same amount of fuel is divided into 10,000 spherical particles. In this case the original surface area increases approximately 232 times! When these particles are dispersed in the air, all 232 times the surface area is available to the burning process.
This
exercise helps to demonstrate why a combustible material which is in the form of dust form is
more energetic and presents a danger: the surface area available for the
oxidization reaction is much greater than found with a large chunk of fuel.
This greater surface areas isn't of great concern if the dust is in a pile. The particles pack fairly tightly and reduce the amount of surface area exposed to oxygen. The problems arise when the dust particles are suspended in a cloud. These dust clouds can easily be formed from normal operations.It is the responsibility of the owner/operator of a facility to identify the locations where dust clouds are likely to form and to implement the engineering controls and administrative controls to prevent these clouds from forming. This identification of risks and how they will be managed form the basis for the Dust Hazard Analysis (DHA).
Thursday, June 15, 2017
What is Fire?
We have all seen a fire. But what is it really? In
simplistic terms, fire is a rapid reaction between a material, i.e. the fuel,
and any oxygen in the environment surrounding that fuel, i.e. the oxidizer.
This is the same reaction which creates rust on iron and steel surfaces,
although the rate of the “rusting” reaction is many orders of magnitude slower
than the “burning” reaction. While I suppose it would be technically correct to
say “We melted marshmallows over a camp-rust” or “There was a forest-rust that
destroyed 4,000 acres” it just doesn’t sound correct. We understand the word
“fire” to mean an energetic and rapid release of hot gases and visible flames
and the word “rust” to mean a relatively slow process. Although in wet, humid
environments the rusting can take place in a very short time.
The flames we see during a fire are the visible release of
energy from the oxidation reaction that is occurring on the surface of the
fuel. In most cases the flames are visible but there are some fuels that emit
invisible flames. I can remember seeing video footage of the pit area of a car
race where all the pit members started to act excitedly: they were jumping up
and down, frantically waving their arms, running around. It was just general
chaos. What I didn’t realize was that the fuel they were using did not have
visible flames. Those pit crew members were on fire! (This occurred in the 1981 Indianapolis 500. Rick Mears was the driver and he received 1st and 2nd
degree burns. His crew chief received much worse burns.) There were no visible
signs of the rapid oxidation reaction that was taking place. This incident led
to a change in fuel so that visible flames could be seen if the fuel was
burning.
As a first step look at the basic oxidation reaction for
methane (CH4):
Two sides of the fire triangle are represented in this
equation: fuel and oxidizer. The left side of this equation is before the
reaction takes place and there is a fuel (CH4) and an oxidizer (O2)
present. If you have a methane and oxygen mixture and an ignition source is
present, the reaction occurs. After the reaction (the arrow), there are two
different substances present: carbon dioxide and water. The reaction also releases
a lot of heat.
The oxidization reaction for rusting iron (Fe) is:
Like the reaction equation for methane, the left side of the
equation contains a fuel (Fe) and an oxidizer (O2). The right side
contains the products of combustion. Besides the fact that one fuel is a gas
and one is a solid, the primary differences between these two reactions are:
- The activation energy for the iron oxidation (rusting) is much lower than that required to start the burning process for methane.
- The amount of heat released by the rusting iron is less than heat released by the burning methane.
- The rate of the methane oxidation is much faster than the iron oxidation.
So fire is basically the same reaction as the rusting of
those old garden tools stored in the shed. It occurs many times faster than the
rusting process but it is the same reaction: the oxidation of a material.
Monday, June 12, 2017
Explosion Kills 4 in Cambria, WI
On Wednesday May 31, 2017 a powerful explosion destroyed
much of a corn mill located in Cambria, Wisconsin. According to Fox 6 Now three
workers were killed in the blast with the fourth victim succumbing to his
injuries on June 6th, 2017. Along with the four fatalities, eleven others were
injured in the explosion. An investigation into the cause of the blast is
underway but the cause of the explosion is unknown at this time. However one
potential cause that is being investigated is a dust explosion.
Dust explosion are typically caused when a cloud of
combustible dust reaches a critical concentration and is ignited by some energy
source. Once ignited, the dust cloud rapidly burns and, if it occurs in an
enclosed space, results in a rapid pressure increase and an explosion. Large
amounts of combustible dust are present in many workplaces, especially in
facilities that handle grain, but the risk is frequently underestimated.
According to NFPA 652 it is the responsibility of the owner/operator of a
facility to conduct a Dust Hazard Analysis (DHA) to determine the risks present
in their facility and to develop and implement a plan to manage those risks. This plan also needs to include training for all employees and contractors so that they can recognize the risks created by combustible dust.
No matter what caused the explosion in Wisconsin, it should
remind all of us that risks are present in our workplaces. Safety is not just
the first agenda item in a meeting: it needs to be part of our everyday
procedures and every task we perform. All of us, from the CEO on down to the
newest untrained employee, need to be on the lookout for the hazards around us.
This is especially true if the hazard is a combustible dust. Because if a dust
explosion occurs, it will likely have devastating consequences.
Monday, June 5, 2017
The Triangle, the Quadrilateral, and the Pentagon
One of the tools used to teach people about the danger of
fire is the fire triangle. The triangle is used because there are three
elements needed for a fire to occur: fuel, oxidizing agent, and an ignition
source. The fuel is what burns be it a solid (wood, coal) or a gas (natural gas,
gasoline or alcohol vapors). (Liquids don’t actually burn; it is the vapor
above the liquid which burns.) The oxidizing agent is typically the oxygen present
in the atmosphere. The ignition source can be an open flame, an electric spark,
or even a hot surface. Combining these three elements typically results in a
fire. If one or two of these elements are taken away, a fire will be
extinguished.
In order to have a dust fire, a fourth element is typically
required: dispersion. If a dust is in a pile or a layer, it will typically not
burn due to the limited amount of oxygen and surface area exposed to the oxygen
and ignition source. This statement is generally true and depends upon the
flammability of the particular powder that is being exposed to the ignition
source. But when the dust or powder is dispersed in the atmosphere, the amount
of surface area exposed to the oxidant and the ignition source increase by
orders of magnitude. The large amount of surface area of the dust can experience
a rapid oxidation reaction and take the form of a flash fire. Technically
speaking, this flash fire is a deflagration. If deflagration occurs in an open
area the heat and products of combustion are free to expand. This expansion creates
a large amount of radiant heat and a pressure wave. But since it is uncontained,
the effects are primarily localized to the vicinity of the flash fire.
In order to have a dust explosion, a fifth element is
required: containment. When a deflagration occurs within a contained area, the
rapid expansion of the heat and products of combustion cannot freely expand.
This causes the pressure within the containment structure to rise rapidly. If
the pressure rise is sufficient the containment structure will fail violently
and rapidly. This failure is the explosion.
It is important to realize that if these five components are
present and dust explosion is likely. In order to avoid a dust explosion one or
more of these components need to be removed from the area.
In manufacturing plants that create or handle dusts or
powders, these five elements are present in various amounts throughout the
facility. It is the responsibility of the owner/operator of every facility to
carefully consider the processes in their plant and determine how these five elements
are to be controlled, both within the process stream and within the building
itself.
Friday, June 2, 2017
Press
Release
Dust
Explosion: Is Your Facility at Risk?
June 2, 2017
Colorado
Springs, CO – Dust
explosions occur every year, killing and injuring workers and damaging
property. The National Fire Protection Association (NFPA) has issued new
standards that apply to all companies that handle potentially combustible dust.
Keith D. Robinson, P.E. announces that he will be giving a presentation that
will discuss the factors that cause dust explosions and give an overview of the
new NFPA standards. The intended audience is Environment Health and Safety
(EH&S) personnel and facility managers. However, anyone interested in this
topic may attend.
Space is
limited. Please call or email to reserve a spot.
Time
& Date
July 19, 2017
11 AM
Location
Library
21c: Ent Conference Center
1175
Chapel Hill Drive
Colorado Springs, CO 80920
Colorado Springs, CO 80920
This
event is not endorsed by or affiliated with the Pikes Peak Library District.
Contact
To learn more about this presentation
or to reserve your spot, please contact
Keith D. Robinson, P.E.
4966 Daybreak Cir
Colorado Springs, CO 80917
303-746-8904
Monday, May 2, 2016
OSHA and MSHA
In the United States there are two agencies responsible for workplace safety: the Occupational Safety and Health Administration (OSHA) and the Mine Safety and Health Administration (MSHA). These two agencies are part of the US Department of Labor and are under the administration of the Secretary of Labor. Generally speaking, OSHA is responsible for safety regulations covering general industry and construction while MSHA is responsible for safety covering mining and other mineral based industries. The actual distinction between the jurisdictions of the two organizations are far more complex than my simple definition. If you search for the phrase "OSHA vs. MSHA jurisdiction" you will find a long list of articles about the sometimes not so clear jurisdictional boundaries.
While the two organizations are tasked with similar responsibilities in their respective jurisdictions, they have separate rules and regulations and enforcement procedures. At times these can be remarkably similar and at other times remarkably different. In the gray areas where the lines between the jurisdictions are blurred, operators can be in compliance with the rules of one organization and find itself out of compliance with the rules of the other organization. It is very important that the operator of any facility understand which set of rules govern their operation.
Please remember that I am not an attorney or expert of the law. I am just an engineer that has worked on a fair number of production facilities (both OSHA and MSHA jurisdiction) and interacted with Environmental, Health and Safety (EH&S) personnel whose job is to make sure that the workers are safe AND the applicable regulations are being followed. The things in this blog are not legal or even formal engineering recommendations. If you run into a situation about OSHA/MSHA compliance or procedure, go to a pro. Based on what I have read, you will need a professional who understands the process, the language, and the regulations. If you try to go it alone you risk scuttling your case due to procedural errors even if you have a rock solid, no way to lose case.
While the two organizations are tasked with similar responsibilities in their respective jurisdictions, they have separate rules and regulations and enforcement procedures. At times these can be remarkably similar and at other times remarkably different. In the gray areas where the lines between the jurisdictions are blurred, operators can be in compliance with the rules of one organization and find itself out of compliance with the rules of the other organization. It is very important that the operator of any facility understand which set of rules govern their operation.
Please remember that I am not an attorney or expert of the law. I am just an engineer that has worked on a fair number of production facilities (both OSHA and MSHA jurisdiction) and interacted with Environmental, Health and Safety (EH&S) personnel whose job is to make sure that the workers are safe AND the applicable regulations are being followed. The things in this blog are not legal or even formal engineering recommendations. If you run into a situation about OSHA/MSHA compliance or procedure, go to a pro. Based on what I have read, you will need a professional who understands the process, the language, and the regulations. If you try to go it alone you risk scuttling your case due to procedural errors even if you have a rock solid, no way to lose case.
Monday, April 25, 2016
Willful Violations = Prison
Over the past few weeks two high profiles cases about business executives or business owners being sentenced to prison for fatal workplace accidents.
The first case comes under the jurisdiction of OSHA and is high profile mainly because it was referenced in a couple of publications/websites dedicated to industrial hygiene and safety. According to montgomerynews.com the owner of a roofing business was sentenced to 10 months in prison after pleading guilty to charges stemming from the death of an employee. The employee died when he fell approximately 45 ft from a scaffold while performing roof repairs on a church. There were several charges resulting from the incident which included four counts of making false statements, one count of obstruction of justice, and one count of willfully violating an Occupational Safety and Health Administration regulation causing death to an employee. (According to OSHA.gov "A willful violation is defined as a violation in which the employer either knowingly failed to comply with a legal requirement (purposeful disregard) or acted with plain indifference to employee safety."). In this case, the willful violation was due to the owner not supplying fall protection to his employees. The other charges stemmed from false statements made during the subsequent investigation.
The second case has had national and international news coverage. According to the U.S. Department of Justice (justice.gov) Don Blankenship the former Massey Energy CEO was sentenced on April 6, 2016 "...to a year in federal prison and ordered to pay a $250,000 fine." He was sentenced after being found guilty of conspiracy to willfully violate mine health and safety standards. The charges were the results of a catastrophic mine explosion in April 2010 at the Upper Big Branch coal mine that killed 29 miners. The one year sentence is the maximum allowed for that charge.
Blankenship was acquitted of two charges of making false statements that would have carried the chance of much longer sentences. A Massey mine supervisor was sentenced to 21 months in prison for instructing an electrician to disable a methane monitor and another executive was sentenced to 42 months for pleading guilty to charges that he helped evade surprise mine inspections. Blankenship maintains that he did not commit a crime and will appeal the convictions.
The first case comes under the jurisdiction of OSHA and is high profile mainly because it was referenced in a couple of publications/websites dedicated to industrial hygiene and safety. According to montgomerynews.com the owner of a roofing business was sentenced to 10 months in prison after pleading guilty to charges stemming from the death of an employee. The employee died when he fell approximately 45 ft from a scaffold while performing roof repairs on a church. There were several charges resulting from the incident which included four counts of making false statements, one count of obstruction of justice, and one count of willfully violating an Occupational Safety and Health Administration regulation causing death to an employee. (According to OSHA.gov "A willful violation is defined as a violation in which the employer either knowingly failed to comply with a legal requirement (purposeful disregard) or acted with plain indifference to employee safety."). In this case, the willful violation was due to the owner not supplying fall protection to his employees. The other charges stemmed from false statements made during the subsequent investigation.
The second case has had national and international news coverage. According to the U.S. Department of Justice (justice.gov) Don Blankenship the former Massey Energy CEO was sentenced on April 6, 2016 "...to a year in federal prison and ordered to pay a $250,000 fine." He was sentenced after being found guilty of conspiracy to willfully violate mine health and safety standards. The charges were the results of a catastrophic mine explosion in April 2010 at the Upper Big Branch coal mine that killed 29 miners. The one year sentence is the maximum allowed for that charge.
Blankenship was acquitted of two charges of making false statements that would have carried the chance of much longer sentences. A Massey mine supervisor was sentenced to 21 months in prison for instructing an electrician to disable a methane monitor and another executive was sentenced to 42 months for pleading guilty to charges that he helped evade surprise mine inspections. Blankenship maintains that he did not commit a crime and will appeal the convictions.
Tuesday, April 19, 2016
GIGO Revisited
Last week I ordered a few small parts from a large, well known supplier. I had been thinking about ordering these for a while but had been putting it off. Then they sent me an email coupon for free shipping and it got me off of the fence and I ordered the parts. The total of the order was around $250. The online catalog indicated that the items "Usually Ship the Same Day". After a few days I hadn't received an email telling me that the order had shipped so I got online to check the status. When I opened my order summary, I was a bit surprised with what I found:
Wow! That is a bit excessive. For that price Scotty should have been beamed the parts to me instantaneously. After a quick phone call to Customer Service the error was fixed and things are back to the way they should be.
In this case the error was harmless. The company didn't try to charge me $10,000,000 dollars and essentially it was just a typo on a website. But what if this data field were controlling something important?
Way back I wrote about GIGO and blindly trusting the output we get from computers. This glitch illustrates how the computer systems just do what they are told to do by their programmers. If we tell them to do the wrong thing, they will gladly do it, even if it results in disaster. In computer simulations if we put in the wrong boundary conditions, use poor meshing techniques, or even stop the iterations before the solution is converged, we risk basing our designs on flawed data. Any computer simulation must be compared to some benchmark or undergo some sort of "sanity" test. Without these checks, the risk of failures increase dramatically.
Monday, April 11, 2016
Engineering Blog Disclaimer
I need to make sure that every so often I write a disclaimer about the contents of this blog. I am a registered/licensed Professional Engineer in Colorado and several other states (Colorado is my primary state). According to the laws in Colorado (the other states are virtually identical): "Registrants shall at all times recognize that their primary obligation is to protect the safety, health, property, and welfare of the public."
In order to fulfill this obligation, I spend a lot of time performing analysis, simulations, design reviews, etc. for each particular project on which I am working. I am selective on which projects I will assume "Responsible Charge" and subsequently the engineering responsibility. Nothing in this blog should be construed as engineering advice in terms of specific projects or designs. The topics I write about will give general or background information only. Due to space limitations and the goal of a blog, the concepts are necessarily simplified, generalized, and not complete. Because of the general nature of the information, it cannot be blindly used as a design basis or a "how to" manual. For a complete view, consult one of the myriad of textbooks on the subjects I write about or take classes at your local university or college.
Unless it is specifically stated otherwise, I am not in "Responsible Charge" for any project or design that may use the information I have presented as a basis for the design. Anyone reading this blog should use the information I present as a beginning point for their own investigation into a subject matter. If you do want my professional help on a particular project and you want to hire me, please visit my webpage at kdrobinsonpe.com and contact me.
In order to fulfill this obligation, I spend a lot of time performing analysis, simulations, design reviews, etc. for each particular project on which I am working. I am selective on which projects I will assume "Responsible Charge" and subsequently the engineering responsibility. Nothing in this blog should be construed as engineering advice in terms of specific projects or designs. The topics I write about will give general or background information only. Due to space limitations and the goal of a blog, the concepts are necessarily simplified, generalized, and not complete. Because of the general nature of the information, it cannot be blindly used as a design basis or a "how to" manual. For a complete view, consult one of the myriad of textbooks on the subjects I write about or take classes at your local university or college.
Unless it is specifically stated otherwise, I am not in "Responsible Charge" for any project or design that may use the information I have presented as a basis for the design. Anyone reading this blog should use the information I present as a beginning point for their own investigation into a subject matter. If you do want my professional help on a particular project and you want to hire me, please visit my webpage at kdrobinsonpe.com and contact me.
Monday, April 4, 2016
Confined Spaces
You may be asking yourself "What is a confined space?" The official definition contained in the Code of Federal Regulations (29 CFR 1910.146(a)) is:
"Confined space" means a space that: (1) Is large enough and so configured that an employee can bodily enter and perform assigned work; and (2) Has limited or restricted means for entry or exit (for example, tanks, vessels, silos, storage bins, hoppers, vaults, and pits are spaces that may have limited means of entry.); and (3) Is not designed for continuous employee occupancy.
Confined spaces are divided into two types: Permit confined spaces and Non-Permit confined spaces. The definitions of these are also given in 29 CFD 1910.146(a):
"Non-permit confined space" means a confined space that does not contain or, with respect to atmospheric hazards, have the potential to contain any hazard capable of causing death or serious physical harm.
"Permit-required confined space (permit space)" means a confined space that has one or more of the following characteristics:
(1) Contains or has a potential to contain a hazardous atmosphere;
(2) Contains a material that has the potential for engulfing an entrant;
(3) Has an internal configuration such that an entrant could be trapped or asphyxiated by inwardly converging walls or by a floor which slopes downward and tapers to a smaller cross-section; or
(4) Contains any other recognized serious safety or health hazard.
Basically, if there are hazards or potential hazards within a room or area that meets the definition of "Confined Space" then it is a Permit Required Space. It is an employers duty to examine their workplace and determine if confined spaces exist and, if they do exist, evaluate each them and determine if they are "Permit" or "Non-Permit" spaces.
If permit spaces exist and the employer decides the employees WILL NOT enter the Permit space, then it is the employers responsibility to:
1. Warn employees of the danger with signs or "equally effective" means. (The employer must tell the employees that the dangers exist.)
2. Take effective measures to prevent employees from entering the permit spaces. (It is not enough to say "Don't go in there".)
3. Reevaluate any confined space if the use or configuration changes. (This is to make sure that a space isn't mistakenly classified as a "Non-Permit" space.)
4. Inform the contractor of the danger and ensure that any contractor employees that enter a space follow a permit program that is in accordance with 29 CFR 1910.
If permit spaces exist and the employer decides that employees will enter the permit spaces, then it is the employer's responsibility to develop AND implement a written Permit Space Plan in accordance to 29 CFR 1910. This plan must be made available for inspection by employees. Without going into any details about a written plan, it basically is a plan that describes;
1. How the hazards will be removed from the space.
2. How the workers will be protected from the hazards that exist within the space.
3, How injured or incapacitated workers will be removed from the space without exposing other workers to risk.
4. What emergency and/or medical equipment will be supplied.
5. Identifies the number of people that must be involved in any entry into a permit space and outlines the responsibilities of each team member.
The specifics of each plan are left to individual employer to develop since each work site is different and has different hazards.
"Confined space" means a space that: (1) Is large enough and so configured that an employee can bodily enter and perform assigned work; and (2) Has limited or restricted means for entry or exit (for example, tanks, vessels, silos, storage bins, hoppers, vaults, and pits are spaces that may have limited means of entry.); and (3) Is not designed for continuous employee occupancy.
Confined spaces are divided into two types: Permit confined spaces and Non-Permit confined spaces. The definitions of these are also given in 29 CFD 1910.146(a):
"Non-permit confined space" means a confined space that does not contain or, with respect to atmospheric hazards, have the potential to contain any hazard capable of causing death or serious physical harm.
"Permit-required confined space (permit space)" means a confined space that has one or more of the following characteristics:
(1) Contains or has a potential to contain a hazardous atmosphere;
(2) Contains a material that has the potential for engulfing an entrant;
(3) Has an internal configuration such that an entrant could be trapped or asphyxiated by inwardly converging walls or by a floor which slopes downward and tapers to a smaller cross-section; or
(4) Contains any other recognized serious safety or health hazard.
Basically, if there are hazards or potential hazards within a room or area that meets the definition of "Confined Space" then it is a Permit Required Space. It is an employers duty to examine their workplace and determine if confined spaces exist and, if they do exist, evaluate each them and determine if they are "Permit" or "Non-Permit" spaces.
If permit spaces exist and the employer decides the employees WILL NOT enter the Permit space, then it is the employers responsibility to:
1. Warn employees of the danger with signs or "equally effective" means. (The employer must tell the employees that the dangers exist.)
2. Take effective measures to prevent employees from entering the permit spaces. (It is not enough to say "Don't go in there".)
3. Reevaluate any confined space if the use or configuration changes. (This is to make sure that a space isn't mistakenly classified as a "Non-Permit" space.)
4. Inform the contractor of the danger and ensure that any contractor employees that enter a space follow a permit program that is in accordance with 29 CFR 1910.
If permit spaces exist and the employer decides that employees will enter the permit spaces, then it is the employer's responsibility to develop AND implement a written Permit Space Plan in accordance to 29 CFR 1910. This plan must be made available for inspection by employees. Without going into any details about a written plan, it basically is a plan that describes;
1. How the hazards will be removed from the space.
2. How the workers will be protected from the hazards that exist within the space.
3, How injured or incapacitated workers will be removed from the space without exposing other workers to risk.
4. What emergency and/or medical equipment will be supplied.
5. Identifies the number of people that must be involved in any entry into a permit space and outlines the responsibilities of each team member.
The specifics of each plan are left to individual employer to develop since each work site is different and has different hazards.
There are a few places around the home that would qualify as confined spaces such as crawl spaces or attics. These two areas are large enough to enter and "do work", they are not designed for continuous occupancy and they typically have limited or restricted means of entry. Generally speaking, most crawl spaces and attics would qualify as "Non-permit confined spaces". I used to live in a house whose furnace was located in the crawl space that had so many Black Widow and Brown Recluse spiders that I think it met condition (4) above and actually should have been a Permit Space! In all seriousness, since the furnace was located in the crawl space, there was potential for a buildup of carbon monoxide (CO) within the space and so it would meet characteristic (1) listed above. If a furnace technician were to enter the crawl space to work on the furnace, it could qualify as a Permit Space and the technician would need to follow a procedure to ensure that the atmosphere was not hazardous and the other elements contained within a Permit Space Entry plan.
Monday, March 28, 2016
Flow Induced Vibration Part 2: Using CFD to find the forcing frequencies
Combining CFD with FEA can provide a powerful method to investigate flow induced vibration. In Part 1 of this post, the use of FEA to find the natural frequency of the spray lance was discussed. In this post, the use of CFD to find the frequencies found in the velocity fluctuations as the fluid flows across the spray lance.
The spray lance shown in the previous post was designed to be inserted into a vertical column with a turbulent airflow. An important question that had to be answered was whether the flow across the spray lance would induce vibrations within the spray lance that would lead to vibration or even to failure. Since the system was in the design phase, it was necessary to use computer simulations to investigate the expected performance of the system. A transient CFD analysis was performed to estimate the velocities that would be found within the system during normal operation.
The plot below shows the fluctuation in the average velocity along the length the spray lance as determined from the transient CFD analysis. This plot shows that significant fluctuations in the velocity can be expected and, as a result, fluctuations in the forces acting on the spray lance.
A Fourier analysis of this velocity signal yielded a frequency spectrum for this velocity profile as shown in the figure below. This plot shows that the primary frequencies of the velocity are found below 10 Hz, with the two main frequencies at approximately 2-4 Hz.
This second look shows that there are no strong forcing frequencies found at the first or second natural frequencies of the spray lance. Like the results from the velocity analysis, these results also suggest that the configuration is unlikely to experience vibration due to the flow across the spray lance.
The method outlined in these two posts is a simple approach to looking at flow induced vibration. A complete analysis is far more complicated and takes more factors into account. This method however can be used as a screening tool to find potential problems. For example, if the velocity were at or near the critical velocity or if the frequencies in the velocity were found to be near the natural frequency of the spray lance, it would indicate that there was a strong possibility that excessive vibration would exist when the system was started. In this were indeed the case, more investigation or a redesign of the spray lance would be required.
Monday, March 21, 2016
Flow Induced Vibration Part 1: Using FEA to determine the natural frequency
In a recent project I had to design a spray lance to be inserted into a large vertical column. In an early design iteration, it was necessary to determine if the spray lance would suffer from flow induced vibration once the system was started. Since the system did not exist and there was no data about how it actually worked, a computer study of the system was performed to investigate the possibility of flow induced vibration.
One of the useful tools in most FEA packages is the ability to determine the natural frequency of a part very quickly. Using FEA to determine the natural frequency rather than a using a hand calculation can help reduce the time and effort required to study the dynamics of a system. This is especially true if a part undergoes many design changes and the FEA package is linked to or part of the CAD package.
Knowing the natural frequency of a part is important when dealing with turbulent fluid flow or rotating machinery because if the natural frequency of a part happens to be close to the frequency of some forcing function that exists within a system the part is likely to fail at loads far below what a static analysis predicts. This occurs due to the fact that if the forcing function matches the natural frequency, the amplitude of the deflection due to the forcing function is magnified with each cycle, eventually leading to failure. This behavior is called resonance and in almost all engineering cases, is a very bad thing.
In the video example above, the first five calculated natural frequencies for the spray lance are 12.7 Hz, 14.7 Hz, 79.1 Hz, 90.4 Hz, and 218.4 Hz.
As fluids flow across cylinders and other shapes, they can create a regular vortex pattern downstream of the shape. The frequency of these vortices can be expressed using the Strouhal Number which varies primarily as a function of shape and Reynolds number. In this case, the average fluid properties and velocity were used to calculate the Reynolds number across the spray lance to see if it falls within the zone (below Re<300,000) where vortex shedding occurs. In this case, the Reynolds number is approximately 3,600 which is in the vortex shedding zone. At this Reynolds number, the Strouhal Number is approximately 0.21. As a result, the critical velocity where the frequency of the vortex shedding equals the first two natural frequencies are 15.1 ft/s for the first natural frequency and 17.5 ft/s for the second natural frequency. The average velocity along the spray lance was found to be approximately 4.6 ft/s. At this velocity, the frequency of vortex shedding is approximately 3.9 Hz, which is well below the first natural frequency of 12.7 Hz. The fact that the average velocity is well below the first critical velocity suggests that the likelihood for vibration due to the vortex shedding is low.
Monday, March 14, 2016
Part 2: What is the basis for using ACH as a design parameter?
In a previous post I examined how the concentration of a
pollutant decreased over time as a function of different ventilation rates. This
examination was limited to the case where the pollutant was at some fixed
level in a space and then ventilation was introduced into that space. An example
of this situation would be a pollutant leaking from a pipe into a closed room and then a valve
being closed which stops the flow of the pollutant and then a fan being turned on to provide ventilation to the space. While this scenario is
possible, it is probably more useful to examine the case where a pollutant is
being emitted at some rate and ventilation is being supplied to attempt control
the level of that pollutant. For simplicity, it will be assumed that the
initial concentration of the pollutant is zero. With this simplifying assumption,
this case can be modeled using a relatively simple differential equation:
where C(t) =
Concentration at time t
G = Generation rate of pollutant
Q = Ventilation rate
V = Volume of the space
Dt = Change in time
This equation comes from ACGIH's book Industrial Ventilation A Manual of Recommended Practice. As with the previous case, the units for each of the parameters must be consistent.
If G is given in CFM, then the time will be minutes and the volume will need to
be given in cubic feet. So what impact does changing the ACH have upon the
concentration of the pollutant in a space? For this example, it is assumed that
the rate of pollutant generation is 1 CFM (0.5 L/s) in a room with a volume of
10,000 cubic feet (283 cubic meters), a space roughly 29’ wide x 29’ long x 12’
tall (8.8 m x 8.8 m x 3.7 m).
As in the previous case, the ACH has a dramatic impact upon the
final concentration of the pollutant in the room. At small values for ACH the
concentration of a pollutant increases for quite some time until a steady state
concentration is reached. For example with an ACH = 0.5 the concentration
continues to increase for about 10 hours until the final concentration of
12,000 ppm (1.2% by volume) is reached. Contrast this with an ACH = 4 where the
final concentration of 1,500 ppm (0.15%) is reached after an hour. As ACH increases, the final steady state concentration decreases. This chart suggests that the ventilation rate can be used to control the final concentration of pollutants in a space.
It can be reasonably concluded that using the ACH as a design parameter for
a ventilation system has merit. However, it is necessary to again mention that
several simplifying assumptions were made in the previous analysis which can
have a dramatic effect upon the performance graphs presented here. The limitations
of this method will be examined in an upcoming post.
Tuesday, March 8, 2016
AIHce 2016: Understanding and Using ANSI/AIHA/ASSE Z9.2-2012
Keith D. Robinson, P.E. will be teaching a course entitled PDC 109: Understanding and Using ANSI/AIHA/ASSE Z9.2-2012 at the upcoming AIHce conference. This course provides an in-depth look at the requirements for Local Exhaust Ventilation (LEV) systems that are set forth in this standard. It is intended for Environment Health & Safety (EH&S) personnel, facility managers, system operators, and engineers.
Please visit my main website at www.kdrobinsonpe.com for more information about Keith D. Robinson, P.E.
The System Curve, The Fan Curve, and the Operating Point Lunch and Learn
I am pleased to announce that I will be presenting a complimentary Lunch and Learn session on April 21, 2016 entitled "The System Curve, The Fan Curve, and the Operating Point". During this session, the theoretical background for how a fan and duct system interact will be presented. Following this brief theoretical introduction participants will take flow and pressure measurements on a small duct and fan system to develop the system curve, the fan curve, and the operating point for the system. The skills developed during this session can be used by the participants to determine the performance of the industrial ventilation systems at their individual facilities. A boxed lunch will be provided.
The Lunch and Learn will be held at 12303 Airport Way, Suite 200 in Broomfield, CO. Space is limited to 10 participants. Please contact Keith Robinson at kdr@kdrobinsonpe.com or at 303-746-8904 to reserve your spot.
Please visit my main website at www.kdrobinsonpe.com for more information about this Lunch and Learn or Keith D. Robinson, P.E.
The Lunch and Learn will be held at 12303 Airport Way, Suite 200 in Broomfield, CO. Space is limited to 10 participants. Please contact Keith Robinson at kdr@kdrobinsonpe.com or at 303-746-8904 to reserve your spot.
Please visit my main website at www.kdrobinsonpe.com for more information about this Lunch and Learn or Keith D. Robinson, P.E.
Monday, February 29, 2016
What is the basis for using ACH as a design parameter?
So why is
ACH used as a design parameter? The basis for this comes from the differential
equations that describe concentration buildup and concentration decay. As a
first step, let's examine the concentration decay due to purging. In its basic
form, the concentration decay equation is of the following form:
where C(t) =
Concentration at time t.
C0 = Concentration at time 0
Q = Ventilation
rate
V = Volume of the space
Dt
= Change in time
In the equation, the units need to be in
some consistent format. For example, if the time is given in minutes,
the ventilation rate needs to be given in terms of volumes per
minute. At the same time, the volumetric units used in the ventilation rate
must match the units used to define the space volume such as cubic feet or
cubic meters. For example, if the volume of the room is given in cubic meters
(m3) and the time is given in hours, the ventilation rate must
be given in terms of cubic meters per hour (m3/hr). When the value
of Q is given in terms of cubic feet per hour or cubic meters per hour, the
value of Q/V in the exponent is the ACH.
So how
does changing the ACH effect the concentration of a pollutant in a space?
Figure 1 shows how the concentration of a substance declines based on different
ACH. The abscissa of this graph is change in time while the ordinate is the
ratio of the concentration at a given time to the initial concentration. While there were several simplifying assumptions made in the development of this graph, it shows how increasing the ACH decreases the time required to reduce a concentration of a pollutant.
Based on this simple analysis, it can be stated that using ACH as a design parameter does have a sound basis. However, it must be recognized that it is a very simplified approach. In an upcoming post I will examine how the ventilation rate affects the concentration of a pollutant that is being emitted into a space.