Showing posts with label Industrial Hygiene. Show all posts
Showing posts with label Industrial Hygiene. Show all posts

Monday, April 4, 2016

Confined Spaces

You may be asking yourself "What is a confined space?" The official definition contained in the Code of Federal Regulations (29 CFR 1910.146(a)) is:

"Confined space" means a space that: (1) Is large enough and so configured that an employee can bodily enter and perform assigned work; and (2) Has limited or restricted means for entry or exit (for example, tanks, vessels, silos, storage bins, hoppers, vaults, and pits are spaces that may have limited means of entry.); and (3) Is not designed for continuous employee occupancy.

Confined spaces are divided into two types: Permit confined spaces and Non-Permit confined spaces. The definitions of these are also given in 29 CFD 1910.146(a):

"Non-permit confined space" means a confined space that does not contain or, with respect to atmospheric hazards, have the potential to contain any hazard capable of causing death or serious physical harm. 

"Permit-required confined space (permit space)" means a confined space that has one or more of the following characteristics: 

(1) Contains or has a potential to contain a hazardous atmosphere; 

(2) Contains a material that has the potential for engulfing an entrant; 

(3) Has an internal configuration such that an entrant could be trapped or asphyxiated by inwardly converging walls or by a floor which slopes downward and tapers to a smaller cross-section; or 

(4) Contains any other recognized serious safety or health hazard. 


Basically, if there are hazards or potential hazards within a room or area that meets the definition of "Confined Space" then it is a Permit Required Space. It is an employers duty to examine their workplace and determine if confined spaces exist and, if they do exist, evaluate each them and determine if they are "Permit" or "Non-Permit" spaces.

If permit spaces exist and the employer decides the employees WILL NOT enter the Permit space, then it is the employers responsibility to:
1. Warn employees of the danger with signs or "equally effective" means. (The employer must tell the employees that the dangers exist.)

2. Take effective measures to prevent employees from entering the permit spaces. (It is not enough to say "Don't go in there".)
3. Reevaluate any confined space if the use or configuration changes. (This is to make sure that a space isn't mistakenly classified as a "Non-Permit" space.)
4. Inform the contractor of the danger and ensure that any contractor employees that enter a space follow a permit program that is in accordance with 29 CFR 1910.

If permit spaces exist and the employer decides that employees will enter the permit spaces, then it is the employer's responsibility to develop AND implement a written Permit Space Plan in accordance to 29 CFR 1910. This plan must be made available for inspection by employees. Without going into any details about a written plan, it basically is a plan that describes;

1. How the hazards will be removed from the space.
2. How the workers will be protected from the hazards that exist within the space.
3, How injured or incapacitated workers will be removed from the space without exposing other workers to risk.
4. What emergency and/or medical equipment will be supplied.
5. Identifies the number of people that must be involved in any entry into a permit space and outlines the responsibilities of each team member.

The specifics of each plan are left to individual employer to develop since each work site is different and has different hazards.

There are a few places around the home that would qualify as confined spaces such as crawl spaces or attics. These two areas are large enough to enter and "do work", they are not designed for continuous occupancy and they typically have limited or restricted means of entry. Generally speaking, most crawl spaces and attics would qualify as "Non-permit confined spaces". I used to live in a house whose furnace was located in the crawl space that had so many Black Widow and Brown Recluse spiders that I think it met condition (4) above and actually should have been a Permit Space! In all seriousness, since the furnace was located in the crawl space, there was potential for a buildup of carbon monoxide (CO) within the space and so it would meet characteristic (1) listed above. If a furnace technician were to enter the crawl space to work on the furnace, it could qualify as a Permit Space and the technician would need to follow a procedure to ensure that the atmosphere was not hazardous and the other elements contained within a Permit Space Entry plan.

Monday, March 14, 2016

Part 2: What is the basis for using ACH as a design parameter?

In a previous post I examined how the concentration of a pollutant decreased over time as a function of different ventilation rates. This examination was limited to the case where the pollutant was at some fixed level in a space and then ventilation was introduced into that space. An example of this situation would be a pollutant leaking from a pipe into a closed room and then a valve being closed which stops the flow of the pollutant and then a fan being turned on to provide ventilation to the space. While this scenario is possible, it is probably more useful to examine the case where a pollutant is being emitted at some rate and ventilation is being supplied to attempt control the level of that pollutant. For simplicity, it will be assumed that the initial concentration of the pollutant is zero. With this simplifying assumption, this case can be modeled using a relatively simple differential equation:


where   C(t) = Concentration at time t
G = Generation rate of pollutant
Q = Ventilation rate
V = Volume of the space
Dt = Change in time

This equation comes from ACGIH's book Industrial Ventilation A Manual of Recommended Practice. As with the previous case, the units for each of the parameters must be consistent. If G is given in CFM, then the time will be minutes and the volume will need to be given in cubic feet. So what impact does changing the ACH have upon the concentration of the pollutant in a space? For this example, it is assumed that the rate of pollutant generation is 1 CFM (0.5 L/s) in a room with a volume of 10,000 cubic feet (283 cubic meters), a space roughly 29’ wide x 29’ long x 12’ tall (8.8 m x 8.8 m x 3.7 m).



As in the previous case, the ACH has a dramatic impact upon the final concentration of the pollutant in the room. At small values for ACH the concentration of a pollutant increases for quite some time until a steady state concentration is reached. For example with an ACH = 0.5 the concentration continues to increase for about 10 hours until the final concentration of 12,000 ppm (1.2% by volume) is reached. Contrast this with an ACH = 4 where the final concentration of 1,500 ppm (0.15%) is reached after an hour. As ACH increases, the final steady state concentration decreases. This chart suggests that the ventilation rate can be used to control the final concentration of pollutants in a space.

It can be reasonably concluded that using the ACH as a design parameter for a ventilation system has merit. However, it is necessary to again mention that several simplifying assumptions were made in the previous analysis which can have a dramatic effect upon the performance graphs presented here. The limitations of this method will be examined in an upcoming post.

Tuesday, March 8, 2016

AIHce 2016: Understanding and Using ANSI/AIHA/ASSE Z9.2-2012


See the main conference and expo website here.

Keith D. Robinson, P.E. will be teaching a course entitled PDC 109:  Understanding and Using ANSI/AIHA/ASSE Z9.2-2012 at the upcoming AIHce conference. This course provides an in-depth look at the requirements for Local Exhaust Ventilation (LEV) systems that are set forth in this standard. It is intended for Environment Health & Safety (EH&S) personnel, facility managers, system operators, and engineers. 

Please visit my main website at www.kdrobinsonpe.com for more information about Keith D. Robinson, P.E.

Monday, February 8, 2016

Understanding and Using ANSI/AIHA/ASSE Z9.2-2012

Keith D. Robinson, P.E. will be teaching a course entitled PDC 109:  Understanding and Using ANSI/AIHA/ASSE Z9.2-2012 at the upcoming AIHce conference. This course provides an in-depth look at the requirements for Local Exhaust Ventilation (LEV) systems that are set forth in this standard. It is intended for Environment Health & Safety (EH&S) personnel, facility managers, system operators, and engineers. 

Please visit my main website at www.kdrobinsonpe.com for more information.